Ref : 6T403-AB-M355
*Dimensions are expressed in millimeters, mass in kilograms and reserves represent the ventilation space to be kept around the product for good heat dissipation. The drawing is not contractual.
Notes et options
Options: Adjustment taps, Multi-voltages, Electrostatic screen, Reduced inrush current, Low consumption, Resistance to harmonics, Silent block, caster, Integrated protections, reinforced insulation, Tropicalization, Class II, transformer Factor K5, K7, K9 , High frequencies.
Additional options for the covered versions: Specific color paint, IP21 to IP55, Built-in case with integrated protections, custom housing possible,
Use frequency
50-60Hz
Coupling
Dyn11
Dimensions (L x l x H)
605 x 520 x 645
Fixings: X x Y x ∅ (mm)
440 x 500 x 10
Weight
186
Standard
IEC 60076-11
Winding material
Aluminium
RoHS compliant
Yes
Temperature rise class
Classe H
Eyebolts
Yes
Recommended Electrical Protection Input / Output
DJ D - 80A / DJ C - 63A
Dielectric Input/Output and active/ground
3000V / 3000V
Insulation class
I
Cooling
Air Naturel
IP Indice
IP21